Disconnect switches RPS (RPS-1 100А; RPS-2 250А; RPS-4 400А; RPS-6 630А)
Disconnect switches RPS of open construction with fuses and displaced drive are designed for short-circuit current protection, durational surge currents and rare automatic alternative-current of frequency 50 Hz and voltage 380V switches in distribution panels, board, boxes and other enstallations
Reference designation structure:
RPS-Х/Х Х N3: RPS – disconnect switches with fuses and displaced drive;
- Х – rated current: 1 - 100А; 2 - 250А; 4 - 400А 6-630А;
- Х – shaft length: 1 – 234mm; 2 – 269mm;
- Х – drive disposition: P - right; L - left
- N3 – climatic region modification and placement category GOST 15150-69
Operating conditions:
- above sea level no more than 2000m;
- vibrostability – up to 35 Hz;
- not intended for operating in flameproof and explosive premises with great concentration of current-conductive dust, fumes and destroying insulation chemical deposits;
- not intended for operating in excessive vibration or shock premises;
- operating position is vertical with deviation of to 5° on any side;
- degree of protection IР00 under GOST 14254-96
Technical data of RPS
Parameter | RPS-1 | RPS-2 | RPS-4 | RPS-6 | RPS-10 | RPS-16 |
---|---|---|---|---|---|---|
Rated voltage[V] | 380 | 380 | 380 | 500 | 500 | 500 |
Rated frequency [Hz] | 50 and 60 | 50 and 60 | 50 and 60 | 50 and 60 | 50 and 60 | 50 and 60 |
Rated isolation voltage [V] | 660 | 660 | 660 | 660 | 660 | 660 |
Rated current [A] | 100 | 250 | 400 | 630 | 1000 | 1600 |
АС-20 V | ||||||
Rated short-circuit current [kA] | 20 | 20 | 30 | 32 | 50 | 50 |
Mechanical duration | 500 | |||||
Mechanical operating cycles number | 2500 | |||||
Fuse type | PN2-100 | PN2-250 | PN2-400 | PPN-39 | PPN-41 | PPN-41 |
ТU 3424-015-05755766-2006 | ||||||
Fuse rated power [A] | 100 | 250 | 400 | 630 | 1000 | 1600 |
Fuse maximum power loss [Wt] | 16 | 34 | 56 | 48 | 84 | 90 |