Dry-type transformers from 25 to 2500 kVA are used to step down three-phase voltage of 6 or 10 kV to a lower 0.4 or 0.23 of frequency 50Hz for industrial installations and package transformer substations.
Dry-type transformers are used in industrial and urban uses to minimize hazard and other environmental contamination
Dry-type transformers are used when operating safety, fire resistance, environmental friendly technology and small dimensions are required as liquid-filled types
We offer a full range of dry-type transformers with vacuum cast resin, forced cooling with pumps and funs, in protective housing
Conforms to GOST 11677-85 “Power Transformers. General Application”, GOST 27050-86 “Power transformers size I-III (capacities from 5 to 6300 kVA inclusive, voltage up to 35 kV)”
Technical data of ТS-25..2500 kVA
Rating [kVA] | Circuit version | Ur [kV] | Рsc [W] | Рo [W] | Uo [%] | Io [%] |
25 | У | 10 | 450 | 150 | 4 | 4 |
25 | D | 6 | 450 | 150 | 4 | 4 |
40 | У | 10 | 780 | 220 | 4 | 3 |
40 | D | 6 | 780 | 220 | 4 | 3 |
63 | У | 10 | 1150 | 290 | 4 | 3 |
63 | D | 6 | 1150 | 290 | 4 | 3 |
100 | У | 10 | 1850 | 480 | 4 | 1,35 |
100 | D | 6 | 1700 | 480 | 4 | 1,35 |
160 | У | 10 | 2600 | 670 | 4 | 1,00 |
160 | D | 6 | 2500 | 670 | 4 | 1,00 |
250 | У | 10 | 2900 | 750 | 4 | 0,60 |
250 | D | 6 | 3300 | 750 | 4 | 0,60 |
400 | У | 10 | 4300 | 820 | 6 | 0,40 |
400 | D | 6 | 4800 | 820 | 6 | 0,40 |
630 | У | 10 | 5900 | 1750 | 6 | 0,35 |
630 | D | 6 | 6900 | 1750 | 6 | 0,35 |
1000 | У | 10 | 7900 | 2300 | 6 | 0,30 |
1000 | D | 6 | 9600 | 2300 | 6 | 0,30 |
1600 | У | 10 | 11500 | 3100 | 6 | 0,30 |
1600 | D | 6 | 14000 | 3100 | 6 | 0,30 |
2500 | У | 10 | 17000 | 4300 | 6 | 0,25 |
2500 | D | 6 | 20000 | 4300 | 6 | 0,25 |