Air insulated outdoor switchgear ORU-LE 35, 110, 150, 220 kV

Air insulated outdoor switchgear ORU is designed to receive and distribution in three-phase current of frequency 50 Hz and voltage 35, 110, 150, 220 kV earthed neutral systems electro supply

ORU are used for modular package transformer substation KTPB for rated voltages 35, 110, 150, 220 kV

 

Construction

Air insulated outdoor switchgears are produced from package portable blocks that consist of carrying metal frame with placed equipment, busbar and auxiliary circuit elements.

ORU busbar performed from aluminium pipe. Each block corresponds switchgear open cell and acts as attachment

ORU equipment is installed on pre-engineered and prepared area after foundation assembling

Auxiliary circuit cables are laid in overhead metal or in-ground concrete mold flumes

Energized conducting parts are secured by repair inventory fence for ORU 35, 110, 150, 220 block connection repair production safeguarding

 

Technical data of  ORU 35 kV, PRU 110 kV, ORU 150 kV, ORU 220 kV

Parameter

 

Value for

 ORU 35 kV

Value for

ORU 110 kV

Value for

 ORU 150 kV

Value for ORU220 kV

Rated voltage [kV]

35

110

150

220

Maximum operated voltage [kV]

40,5

126

172

252

Rated current, [А]:

 

 

 

 

 - main circuits

630

630

630

630

 - collecting buses

1000

1000, 2000

1000, 2000

1000, 2000

Initial short-circuit current [кА]

52

52

52

65, 81

Short-time thermal current, 3s [кА]

20

20

20

20, 31,5

Earthing circuits rated voltage [V]

 

 

 

 

  - AC

380/220

380/220

380/220

380/220

  - DC

220

220

220

220

  - voltage transformers

100

100

100

100