Switchgears 2KVE-6 Series

Switchgears 2KVE-6 (LE-E) are designed for placing on turntable in closed unheated space of career excavators and used to three-phase alternative current of frequency 50 or 60 Hz and voltage 6 kV receive and distribution

 

Reference designation structure:

                                       1    2   3       4      5     6

                                    LE-Е-6-(Х)-ХХХХ-ХХ-ХХ

1 – advanced switchgear produced by LVEP “Lider Electrik”;

2 – rated voltage [V];

3 – main circuits scheme number;

4 – rated current [A];

5 – closed current [A];

6 – climatic region and placement category under GOST 15150

 

LE-Е order designation structure:

LE-Е-6-(I)-630-10-NC2  SS U 31.2-35036863-009:2009

 

Technical data of 2КVЕ-6 (LE-Е)

Parameter

Values

Rated voltage [V]

6

Maximum operational voltage [V]

7,2

Current type

alternating

Frequency [Hz]

50

Main circuits rated current [A]

630, 1000

Rated closed current [kA]

10; 20

Short-time thermal current, 3s [kA]

20

Short-time withstand current, 3s [kA]

20

Industrial frequency test voltage, 1min [kV]:

                               - unit

   - second circuit switching

 

32

2

Cycle switching wear Комутаційна зносостійкість циклів:

- at rated current «O-tn-C»

- at rated closing current, «OC»

 

50000

100

Auxiliary placed transformer idling current [A]

1

Total closing time [s]

0,14

Insulation level under GOST 1516.1-76

normal

Insulation level

overhead

Collecting buses insulation level

uninsolated

HV line type connection

cable

Degree of protection under GOST 14254-80

IP32

Withdrawable elements presence

without

Control type

remote, local