Mining normal execution switchgears KRURN-6 LE (LE-RN) are designed to receive and distribute three-phase alternative-current of frequency 50 Hz and voltage of 6 kV in earthed neutral systems for electric installation protection and iron-ores and coal mines, pits, concentrated factories and other mining enterprises underground current receiver control without dust explosion
Applications
KRURN-6 are used for HV motor and iron-ore, miming, coal mines, boring, compressor and other industrial installations connection
Reliability
Conforms to State Standard of Ukraine 31.2-35036863-010:2009
Reference designation structure:
1 2 3 4 5 6
LE-RN-6-ХХ-Х-ХХХ-Х-ХХ
1 – mining normal execution switchgears produced by LVEP “Lider Elektrik”;
2 – rated voltage [kV];
3 – scheme number;
4 – rated current [A];
5 – remote control board type (D – with remote-control station, О – without remote-control station);
6 – climatic region and placement category under GOST 15150-69
LE-RN-6 order designation example:
- consist of outgoing lines unit KRU with single-phase earth-fault directional, minimal voltage without delay at rated current 100A protection and remote-control station in case of order:
LE-RN-6–О1-О-100-D NC5 SS U 31.2-35036863-010:2009
-KRU without remote-control station consist of input at 630A, outgoing lines at 200 A, sectional at 315 A, outgoing lines at 50 A and input at 630 A units:
LE-RN-6–V2-G-630-0; О1-G–200-0; S1-G–315-0; О1-G–050; V2-G–630-0 NC5 SS U 31.2-35036863-010:2009
Dimensions and weights of KRURN-6 LE (LE-N)
Dimensions [mm] (without placed voltage transformer) | Weight approx. [kg] | ||
Width | Height | Depth | |
800 | 1700 | 1400 | 890 |
Technical data of KRUN-6 LE (LE-N)
Parameters | Values |
Rated voltage [kV] | 6 |
Maximum operating voltage [kV] | 7,2 |
Current type | alternating |
Frequency [Hz] | 50 |
Main circuit rated current: input and sectional units outgoing lines units |
315; 400; 630 50; 100; 160; 200; 315; 400 |
Mechanical duration number | 50000 |
Switching duration number at rated current | 50000 |
Rated closed current [kA]: unit switch |
10 20 |
Rated open current values [kA]: maximum peak start active value |
25
10 |
Short-time withstand current [kA] | 25 |
Short-time thermal current, 1s [kA] | 10 |
Thermal withstand index **, [kА2s] | 300 |
Maximum acceptable rated closing current number | 100 |
Switching wear duration number at rated closing current | 30000 |
Mining designation under GOST 24719 and GOST 24754 | MN1 |
Degree of protection under GOST 14254 | IP54 |
Outgoing line type | cable |