Medium voltage indoor vacuum circuit breaker BB-LE-12.5 is designed to three-phase alternative-current of frequency 50 Hz and voltage up to 12 kV distributional systems switch in normal and emergency operational modes
Applications
Vacuum circuit breakers BB-LE-12.5 are used in switchgear units with voltage 6 or 10 kV and substations 110/10(6), 35/10(6), 10(6)/0.4 kV for infrastructure, metallurgical, producing, petrochemical industry, power generation facilities
Construction
BB-LE-12.5 corresponds vacuum circuit breaker with firm insulation and encapsulated in epoxy resin pole units
Vacuum interrupters use petal type contacts for superior dielectric strength and better performance characteristics
Vacuum circuit breaker ВВ-LE-12,5 can be mounted on a withdrawable part
Reliability
Conforms to State Standard of Ukraine 27.1-35036863-018:2014
Reference designation structure
1 2 3 4 5 6 7
ВВ-LE-12,5-ХХ/ХХХХ-ХХХх-ХХ
1 – Vacuum circuit breaker
2 – Rated operational voltage [kV]
3 – Turn-off rated current [A]
4 – Rated current [A]
5 – Pole-center distance [mm]
6 – Modification:
S – fixed;
В –withdrawable
7 –Climatic region modification und placement category under GOST 15150
Order designation example:
ВВ-LE-12,5-25/630-150v N3 SS U 27.1-35036863-018:2014
Technical data of BB-LE-12.5
Parameter | Values | ||||||||||||||||
Rated voltage [kV] | 10 | ||||||||||||||||
Rated operational voltage [kV] | 12.5 | ||||||||||||||||
Short withstand voltage [kV] | 42 | ||||||||||||||||
Storm impulse test voltage [kV] | 75 | ||||||||||||||||
Rated frequency [Hz] | 50 | ||||||||||||||||
Rated current [A] | 630 | 1250 | 1600 | 2000, 2500 | 3150, 4000 | ||||||||||||
Pole-center distances [mm] | 150 | 210 | 150 | 210 | 275 | 210 | 275 | 275 | 275 | ||||||||
Fault clearing rated current [kA] | 25 | 31,5 | 25 | 31,5 | 25 | 31,5 | 25 | 31,5 | 40 | 40 | 31,5 | 40 | 31,5 | 40 | 31,5 | 40 | 40 |
Short-time current [kA] | 63 | 80 | 63 | 80 | 63 | 80 | 63 | 80 | 100 | 100 | 80 | 100 | 80 | 100 | 80 | 100 | 100 |
Rated operating sequence | C – 0,3 с – O C – 180 с – CO | ||||||||||||||||
Opening time [ms] | 20 – 50 | ||||||||||||||||
Arc extinction time [ms] | ≤ 15 | ||||||||||||||||
Closing time [ms] | 30 – 70 | ||||||||||||||||
Average opening speed [ms] | 0,5 – 0,8 | ||||||||||||||||
Average closing speed [ms] | 0,9 – 1,2 | ||||||||||||||||
Three-phase opening and closing asynchrony | ≤ 2 |