Outdoor switchgears KRN-10(6) (LE-N) are designed to receive and distribute three-phase alternative-current of frequency 50 Hz and voltage 6 or 10 kV in earthed or insulated neutral systems
Applications
LE-N are used in distribution points of voltage 6 or 10 kV in structure of transformer substations 110/35/10(6) and 35/10(6) kV
Reliability
Conforms to State Standard of Ukraine 31.2-35036863-007:2009
Referense designation structure:
1 2 34 5 6
LE-N-Х-ХХ-ХХ ХХ
1 –Outdoor switchgear
2 – Rated voltage [kV]
3 – Lead-in type (V – overhead, K – cable)
4 – Outgoing type (V – overhead, K – cable)
5 – Main circuit scheme number
6 – Climatic region and placement category under GOST 15150
LE-N order designation example:
LE-N-10-VK-01 N1
Technical data of KRN-10(6) (LE-N)
Parameter | Values |
Rated voltage [kV] | 6; 10 |
Rated operating voltage [kV] | 7,2; 12 |
Main circuits rated power [A] | 630; 1000; 1600 |
Collecting buses rated current [A] | 1000; 1600; 2000; 2500; 3150 |
Switch rated closing current [kA] | 12,5; 16; 20; 25; 31,5 |
Short-time thermal current, 3s [kA] | 20; 31,5 |
Short-time withstand current [kA] | 51; 81 |
Secondary circuits rated voltage [V]: DC AC |
110; 220 220 |
Auxiliary placed transformer rated power [kVA] | 25-40 |