Outdoor Mining Switchgears KRUNK-10(6)-LE (LE-NK)
Applications
KRUNK-LE are designed for mobile machine open cast mining electrical equipment internal overhead cables connection 10(6) kV
Reliability
Conforms to State Standard of Ukraine 31.2-35036863-007:2009
Reference designation structure:
1 2 3 4
LE-NK-ХХ-Х ХХ
1 – Outdoor mining switchgear;
2 – Rated voltage, kV;
3 – Modification (S – fixed, P – portable);
4 – Climatic region modification and placement category under GOST 15150
KRN order designation example:
KRUNK (LE-NK)-6-P-LE N1
Technical data of KRUNK-10(6)-LE (LE-NK)
Parameter | Values |
Rated voltage [kV] | 6; 10 |
Maximum operational voltage [kV] | 7,2; 12 |
Main circuits rated current with frequency 50 Hz [A] | 630; 1000 |
Closed rated current [kA] | 20; 31,5 |
Short-time withstand current [kA] | 41 |
Short-time thermal current, 3s [kA] | 20; 31,5 |
Test voltage of industrial frequency [kV] | 31; 42 |
Lead-in type | cable, overhead |
Insulation level under GOST 1516.1-76 | normal |
Degree of protection under GOST 14254-96 | IP43 |